Vacuum Circuit Breaker
SERIES TIPO VZ
Caracteristicas generales
Model Number |
VZ-20J16 |
VZ-20M16 |
VZ-20J25 |
VZ-20M25 |
VZ-20P25 |
|
Maximum Continuous Current |
630A |
1250A |
630A |
1250A |
2000A |
|
Rated Voltage |
24kV |
|||||
Rated Interrupting Current |
16kA |
25kA |
||||
Rated Frequency |
50/60 Hz |
|||||
Rated Making Current |
40kA |
63kA |
||||
Rated Short-Time Current |
16kA - 3 Sec. |
25kA - 3 Sec. |
||||
Rated Interrupting Time |
Less than 3 Cycles |
|||||
Out of Phase Breaking Current |
25% of Rated Interrupting Current |
|||||
Basic Impulse Level (BIL) |
125kV |
|||||
AC Withstand Voltage |
50kV - 1 Min. |
|||||
Operation Duty |
Standard Duty |
O - 3 min. - CO - 3 min. - CO |
||||
Rapid Duty |
O - 0.3s - CO - 3 min. - CO |
|||||
Mechanical Life |
10,000 Operations |
|||||
Load Switching Life |
10,000 Operations |
|||||
Auxiliary Contacts |
Form |
4NO-4NC |
||||
Cont. Current |
20A |
|||||
Voltage |
220V Max. - 48V Min. |
|||||
AC Interrupting |
AC: Make 20A/Break 10A (110V) at PF 0.35 |
|||||
DC Interrupting |
DC: 10A (48V), 5A (110V), 2.5A (220V) at L/R 40 ms |
|||||
Altitude (Above Derate by ANSI C37.04) |
3300 ft (1000 m) |
|||||
Ambient Temperature |
-5 to +40°C |
|||||
Installation |
Fixed or Drawout |
|||||
Operation |
Motor Spring Closing |
|||||
Opening Time |
30 ms (Typical) |
|||||
No Load Closing Time |
40 ms |
|||||
Operating - Charging Motor Voltage, Current, Charging Time |
125Vdc, 5A (starting)/0.5A, 0.01s (starting)/7s |
|||||
Closing Voltage, Current |
||||||
125Vdc, 3.2A (Standard) |
||||||
Tripping Voltage, Current |
||||||
125Vdc, 3.2A (Standard) |
||||||
Weight |
298 lb. (135 kg) |
320 (145) |