Vacuum Circuit Breaker
SERIES TIPO VK / HVK
Caracteristicas generales
Identification |
Rated Values |
Related Required Capabilities |
|||||||||||||
ANSI Line No. |
Type-Form of Breaker |
Nominal rms Voltage Class (kV) |
Nominal 3-phase Class (MVA) |
Voltage |
Insulation Level |
Current |
Rated Inter-rupting Time (Cycles) |
Rated Per-Missable Tripping Delay, Y (Seconds) |
Rated Maximum rms Voltage Divided by K (kV) |
Current Values |
|||||
Rated Maximum rms Voltage (kV)(2)* |
Rated Voltage Range Factor, K (3)* |
Rated Withstand Test Voltage |
Con-tinuous rms Current Rating at 60Hz (A) |
Short-circuit rm*s Current Rating (at Rated Max. kV) (kA)(4)* |
Maximum Symmetrical Interrupting Capability (5)* |
3 Sec Short-time Current Carrying Capability |
Closing and Latching Capability 1.6K Times Rated Short-circuit rms Current(kA) |
||||||||
Low Frequency rms Voltage (kV) |
Crest Impulse Voltage (kV) |
K Times Rated Short-circuit rms Current |
|||||||||||||
(kA) |
(kA) |
||||||||||||||
2 |
VK-6M32A |
4.16 |
250 |
4.76 |
1.24 |
19 |
60 |
1200 |
29 |
3 |
2 |
3.85 |
36 |
36 |
58 |
3 |
VK-6P32A |
4.16 |
250 |
4.76 |
1.24 |
19 |
60 |
2000 |
29 |
3 |
2 |
3.85 |
36 |
36 |
58 |
(1)* |
VK-6M40A |
4.16 |
350 |
4.76 |
1.0 |
19 |
60 |
1200 |
41 |
3 |
2 |
4.76 |
41 |
41 |
66 |
(1)* |
VK-6P40A |
4.16 |
350 |
4.76 |
1.0 |
19 |
60 |
2000 |
41 |
3 |
2 |
4.76 |
41 |
41 |
66 |
4 |
VK-6M50 |
4.16 |
350 |
4.76 |
1.19 |
19 |
60 |
1200 |
41 |
3 |
2 |
4.0 |
49 |
49 |
78 |
|
VK-6P50 |
4.16 |
350 |
4.76 |
1.19 |
19 |
60 |
2000 |
41 |
3 |
2 |
4.0 |
49 |
49 |
78 |
6 |
VK-6Q50 |
4.16 |
350 |
4.76 |
1.19 |
19 |
60 |
3000 |
41 |
3 |
2 |
4.0 |
49 |
49 |
78 |
7 |
VK-8M40A |
7.2 |
500 |
8.25 |
1.25 |
36 |
95 |
1200 |
33 |
3 |
2 |
6.6 |
41 |
41 |
66 |
8 |
VK-8P40A |
7.2 |
500 |
8.25 |
1.25 |
36 |
95 |
2000 |
33 |
3 |
2 |
6.6 |
41 |
41 |
66 |
(1)* |
VK-8Q40 |
7.2 |
500 |
8.25 |
1.25 |
36 |
95 |
3000 |
33 |
3 |
2 |
6.6 |
41 |
41 |
66 |
9 |
VK-10M25A2 |
13.8 |
500 |
15 |
1.30 |
36 |
95 |
1200 |
18 |
3 |
2 |
11.5 |
23 |
23 |
37 |
|
VK-10P25A2 |
13.8 |
500 |
15 |
1.30 |
36 |
95 |
2000 |
18 |
3 |
2 |
11.5 |
23 |
23 |
37 |
11 |
VK-10M40A |
13.8 |
750 |
15 |
1.30 |
36 |
95 |
1200 |
28 |
3 |
2 |
11.5 |
36 |
36 |
58 |
|
VK-10P40A |
13.8 |
750 |
15 |
1.30 |
36 |
95 |
2000 |
28 |
3 |
2 |
11.5 |
36 |
36 |
58 |
(1)* |
VK-10Q40 |
13.8 |
750 |
15 |
1.30 |
36 |
95 |
3000 |
28 |
3 |
2 |
11.5 |
36 |
36 |
58 |
(1)* |
VK-10M40A |
13.8 |
1000 |
15 |
1.0 |
36 |
95 |
1200 |
37 |
3 |
2 |
15 |
37 |
37 |
59 |
|
VK-10P40A |
13.8 |
1000 |
15 |
1.0 |
36 |
95 |
2000 |
37 |
3 |
2 |
15 |
37 |
37 |
59 |
(1)* |
VK-10Q40 |
13.8 |
1000 |
15 |
1.0 |
36 |
95 |
3000 |
37 |
3 |
2 |
15 |
37 |
37 |
59 |
13 |
VK-10M50 |
13.8 |
1000 |
15 |
1.30 |
36 |
95 |
1200 |
37 |
3 |
2 |
11.5 |
48 |
48 |
77 |
14 |
VK-10P50 |
13.8 |
1000 |
15 |
1.30 |
36 |
95 |
2000 |
37 |
3 |
2 |
11.5 |
48 |
48 |
77 |
15 |
VK-10Q50 |
13.8 |
1000 |
15 |
1.30 |
36 |
95 |
3000 |
37 |
3 |
2 |
11.5 |
48 |
48 |
77 |
(1)* |
VK-20J13 |
23 |
500 |
25.8 |
1 |
60 |
125 |
600 |
12 |
3 |
2 |
25.8 |
12 |
12 |
19 |
(1)* |
VY-20M25A |
23 |
1000 |
25.8 |
1.0 |
60 |
125 |
1200 |
20.8 |
3 |
2 |
25.8 |
20.8 |
20.8 |
33.3 |
(1)* |
VY-20P25A |
23 |
1000 |
25.8 |
1.0 |
60 |
125 |
2000 |
20.8 |
3 |
2 |
25.8 |
20.8 |
20.8 |
33.3 |
(1)* |
VY-30M25A |
34.5 |
1500 |
38 |
1.35 |
80 |
150 |
1200 |
21 |
3 |
2 |
28 |
28.4 |
28.4 |
45.5 |
(1)* |
VY-30P25A |
34.5 |
1500 |
38 |
1.35 |
80 |
150 |
2000 |
21 |
3 |
2 |
28 |
28.4 |
28.4 |
45.5 |
*Numbers in parentheses refer to the notes below. |
|||||||||||||||
(1) ANSI C37.06 does not define these ratings. |
|||||||||||||||
(2) Maximum voltage for which the breaker is designed and the upper limit for operation. |
|||||||||||||||
(3) K is the ratio of rated maximum voltage to the lower limit of the range of operating voltage in which the required symmetrical and asymmetrical interrupting capabilities vary in inverse proportion to the operating voltage. |
|||||||||||||||
(4) To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1/K times rated maximum voltage and rated maximum voltage, the following formula shall be used. Required Symmetrical Interrupting Capability= Rated Short-circuit Current X (Rated Max. Voltage)/(Operating Voltage) |
|||||||||||||||
(5) Current values in this column are not to be exceeded even for operating voltages between the rated maximum voltage and 1/K times rated maximum voltage, follow (4) above. |