SERIES TIPO VJB

SERIES TIPO VJB

Vacuum Circuit Breaker

Caracteristicas generales

VJB Series 24kV & 36kV

Item

Type

VJB-20M20F

VJB-20P20F

VJB-30M13F

VJB-30P13F

Voltage

(kV)

24

36

Insulation Level

(kV)

AC-50, Impulse-125

AC-70, Impulse-170

Current (*1)

(A)

1200 / 1250

2000

1200 / 1250

2000

Frequency

(Hz)

50/60

Interrupting Current

(kA)

20

12.5

Interrupting Capacity

(MVA)

830

780

Transient Recovery Voltage

(kV/ms)

0.5

0.6

Closing (Make) Current

(kA)

50

31.5

Short Time Withstand Current-2s (kA)

20

Opening Time

(sec)

0.03

Interrupting Time

(cycle)

3

Closing Time

(sec)

0.25

Standard Operating Duty

A (O - 1 min. - CO - 3 min. - CO)

Closing Operation

Voltage (V)

DC100

Current (A)

90

Closing Voltage Range

(V)

DC 85 ~ 110

Opening Control

Voltage (V)

DC100

Current (A)

4.5

Opening Voltage Range

DC 60 ~ 125

Mechanical Life (*2)

150,000 Times

Electrical Life (*3)

150,000 Times

Contact Wipe

(mm)

7

Allowable Contact Wear

(mm)

3

Number of Auxiliary Contacts (*4)

7a-6b (7NO-6NC)

Installation Method

Floor Mount, Fixed Type

Weight

(kg/lb)

520 / 1146

Applicable Standards

JEC-2300 / IEC 56

Notes:

*1 The rating is fully guaranteed even housed in a dustproof cubicle.

*2 Replace auxiliary switch, control contacts and auxiliary relay after 75,000 operations.

*3 Rated interrupting current can be closed and opened 10 times.

*4 The number of auxiliary switch contacts shown is for externally usable contacts.