Vacuum contactors
CV-10
Caracteristicas generales
CONTACTOR MODEL |
HCV-1JBU |
HCV-1KAU |
HCV-5HA |
HCV-5HAL* |
CV-10HA(L) |
CV-10HB(L) |
HCV-6KAU |
HCV-6KALU* |
|
Rated Voltage |
208-1500V |
2400/4200/6900V(7.2kV max) |
12/15kV |
12/13.8kV (max.) |
2400/4200/6900V(7.2kV max) |
||||
Rated Operational Current |
600A |
720A |
400A |
400A |
720A |
||||
Rated Thermal Current |
600A |
720A |
450A |
450A |
800A |
||||
Interrupting Current |
42,000A |
7000A (4.5kA @7.2kV) |
5kA/4kA |
5000A |
7200A |
||||
Peak Withstand Current |
- |
85 kA (Peak) |
15.8kA |
12.5kA |
20kA |
||||
Short-circuit Making/Breaking Current |
6000A (100 times) |
7200A (100 times) |
6.3kA |
5kA/4kA |
5kA |
8.0A K |
|||
6000A (25 times) |
7200A (25 times) |
"O" - 3min. - "CO" - 3min. - "CO" |
|||||||
Class E1 MVA |
- |
25/50 (36/60) |
120 |
30/60/85 |
|||||
Class E2 MVA |
- |
200/400/570 |
1200MVA |
200/400/600 |
|||||
Withstand Overload Current |
3600A - 30s |
4320A - 30s |
2400A -30s |
1920A - 30s |
4320A - 30s |
||||
6000A - 2s |
7200A - 2s |
4000A - 12s |
- |
- |
|||||
9000A - 1s |
10800A - 1s |
6300A - 2s |
8000A - 1s |
10,800A - 1s |
|||||
30,000A - 0.05s |
36,000A - 0.05s |
- |
- |
- |
|||||
Overcurrent Strength (Peak Value) |
- |
- |
See Coordination Below |
85kA (PEAK) |
|||||
Coordination w/Current-Limiting Fuses |
50kA |
45kA |
- |
Prospective Short-circuit Current 50kA |
- |
||||
Switching Frequency |
1200/Hr |
1200/Hr |
300/Hr |
300/Hr (Latched type 120/Hr) |
600/Hr |
300/Hr |
|||
Mechanical Life*** |
2.5M |
2.5M |
250k |
250k |
1M |
200k |
|||
Electrical Life*** |
500k |
250k |
250k |
100k |
200k |
||||
Impulse Withstand |
15kV |
60kV |
75kV (95kV/110kV w/SA) |
60kV |
|||||
Dielectric Strength |
5.5kV - 1 min. |
22kV-1 Minute |
36kV - 1 Min |
22kV-1 Minute |
|||||
ClosingTime (@120Vac) |
60 - 80 ms |
75 - 100 ms |
120 - 145 ms |
80-100 ms |
|||||
Opening Time (@120Vac) |
50 - 65 ms |
20 - 30 ms |
80 - 90 ms |
30 - 40 ms |
40-55 ms |
||||
Arcing Time |
10 ms or Less |
10 ms or Less |
10 ms or Less |
10 ms or Less |
|||||
Pick-Up Voltage |
85% (Hot) - 70% (Cold) |
85% (Hot) - 70 % (Cold) AC or DC |
|||||||
Drop-Out Voltage |
20% or more of rated control voltage (cold) |
50%(Hot) - 40% (Cold) AC or DC |
|||||||
Tripping Voltage |
- |
60% or less of Coil Rating DC (cold) |
|||||||
Control Voltage |
Standard |
100-240 Vac/dc |
120Vac 50/60 Hz |
100-240Vac/100-250Vdc |
115-240Vac/125-250Vdc |
||||
Optional |
- |
240Vac/125Vdc/250Vdc |
- |
- |
|||||
Control Circuit Burden |
Closing |
1080 VA |
5.4A Peak @120Vac 670VA (AC) - 700W (DC) |
7.2A Peak @120Vac 864VA (AC) - 900W (DC) |
6~7.0A @120Vac 840VA (AC) - 875W (DC) |
||||
Holding |
50 VA |
0.12A Avg. @120Vac 85VA (AC) - 85W (DC) |
0.16A Avg. @120Vac 80VA (AC) - 90W (DC) |
0.8~1.0A @120Vac 48VA |
|||||
Tripping* |
- |
4.8A Peak @125Vdc |
4.8A Peak @125Vdc |
4.8A Peak @125Vdc |
|||||
Auxiliary Contact Ratings |
Arrangement |
3NO-3NC |
3NO-3NC |
2NO-3NC |
4NO-2NC (Latched type 2NO-1NC) |
3NO-3NC |
2NO-2NC |
||
Current |
10A (A600) |
||||||||
Voltage |
600V Max - 48V Min |
||||||||
AC |
720VA (P.F. 0.35) |
||||||||
DC |
60W (L/R 150 ms) |
||||||||
Application Conditions |
Altitude w/o Derate |
Lower than 3300ft (1000m) |
|||||||
Ambient |
-5 to + 40°C |
||||||||
Relative Humidity |
Minimum 45% to Maximum 95% Non-condensing |
||||||||
Vibration |
Max. 20 Hz - 1G |
||||||||
Shock |
Max. 30G |
||||||||
Weight - lbs. (kg) |
59.5 (27) |
61.7 (28) |
43 (19.5) |
44 (20) |
88 (40) |
91 (41) |
60 (27) |
62 (28) |
|
* Latched version. |